CPM BOARD Working Principle:
There
is one CPM per compressor. The device controls the
compressor contactors, oil
solenoid, loading/unloading the
solenoid, motor cooling solenoid (30XA080,082 only) and the
oil separator heater. The CPM also monitors the compressor
motor temperature, high pressure switch, oil level switch, discharge
gas temperature, oil pressure transducer, motor current,
MTA (must trip amps) setting and economizer pressure transducer.
The CPM responds to commands from the MBB (Main
Base Board) and sends the MBB the results of the channels it
monitors via the LEN (Local Equipment Network). The CPM
has three DIP switch input banks, Switch 1 (S1), Switch 2 (S2),
and Switch 3 (S3). The CPM board DIP switch (S1) configures
the board for the type of starter, the location and type of the
current transformers and contactor failure instructions. See Table
4 for description of DIP switch 1 (S1) inputs. See Appendix
D for DIP switch settings.
The CPM board DIP switch S2 setting determines the must
trip amps (MTA) setting. See Appendix D for DIP switch settings.
The MTA setting which is calculated using the settings
S2 must match the MTA setting in the software or an MTA
alarm will be generated.